TECHNICAL SPECIFICATIONS
Model
E180MET33
Phase
3-Phase In / 3-Phase Out
Capacity
100KVA / 90KW
Parallel Capability
2
INPUT
Nominal Voltage
3 x 380/400/415 VAC (3Ph+N)
Voltage Range
208-304 VAC @ 70% load | 305-478 VAC @ 100% load
Frequency Range
40~70 Hz
Power Factor
≧ 0.99 @ 100% Load
Harmonic Distortion (THDi)
< 3% at full linear load
OUTPUT
Output Voltage
3 x 380/400/415 VAC (3Ph+N)
AC Voltage Regulation (Batt. Mode)
± 1%
Frequency Range (Synchronized Range)
46~54Hz or 56~64Hz
Frequency Range
(Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≦ 2 % THD (Linear Load)
≦ 4 % THD (Non-linear Load)
|
|
Waveform (Batt. Mode)
Pure Sinewave
Overload
105-110% for 1 hr, 111-125% for 10 min, 126-150% for 1 min,
>150% for 200ms
BYPASS
Nominal Voltage
3 x 380/400/415 VAC (3Ph+N)
Voltage Range
-30% ~ +20%
Frequency Range (Synchronized Range)
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Overload Capability
105-110% for 1 hr, 111-125% for 10 min, 126-150% for 1 min, >150% for 200ms
EFFICIENCY
AC Mode
94%
ECO Mode
98%
Battery Mode
93%
BATTERY
|
|
INDICATORS
LCD Panel
10″ Touch Type color LCD
ALARM
Battery Mode
Sounding every 2 seconds
Low Battery
Sounding every 0.5 second
Overload
Sounding every second
Fault
Continuously sounding
PHYSICAL
|
|
ENVIRONMENT
Operation Temperture
0 ~ 40°C
Operation Humidity
< 95% and non-condersing
Altitude
0 ~ 1000m at full load
Noise Level
Less than 70dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
Product Variants
ExTell Magna, Tower 3 Phase External Battery 10 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 15 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 20 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 30 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 40 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 60 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 80 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 100 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 120 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 180 KVA Online UPS, PF = 1.0
ExTell Magna, Tower 3 Phase External Battery 200 KVA Online UPS, PF = 1.0
Downloads
FAQ’S
Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry’s standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type specimen book. It has survived not only five centuries, but also the leap into electronic typesetting, remaining essentially unchanged.