Description
Product Overview
Product Variants
Downloads
FAQ’S
Features
TECHNICAL SPECIFICATIONS
Model
E001SET31
Phase
Single phase with ground
Capacity
1000 VA / 800 W
INPUT
Nominal Voltage
110/115/120/127VAC or 208/220/230/240VAC
Input Voltage Range
55-150 VAC or 110-300 VAC (Based on load at 50%)
85-140VAC or 160-280VAC (Based on load at 100%)
Frequency Range
40Hz ~ 70 Hz
Power Factor
≧ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage
110/115/120/127VAC or 208/220/230/240VAC
Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
47~53 Hz or 57~63 Hz
Frequency Range
(Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≦3 % THD (Linear Load), ≦6 % THD (Non-linear Load)
Transfer Time – AC Mode to Battery Mode
Zero
Transfer Time – Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
88%
Battery Mode
83%
BATTERY
|
|
|
|
INDICATORS
LCD
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
PHYSICAL
|
|
|
|
ENVIRONMENT
Humidity
20-90 % RH @ 0 – 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB
Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
Product Variants
ExTell Spectra, Tower Single Phase External Battery 1 KVA Online UPS, PF = 0.8
ExTell Spectra, Tower Single Phase External Battery 2 KVA Online UPS, PF = 0.8
ExTell Spectra, Tower Single Phase External Battery 3 KVA Online UPS, PF = 0.8
ExTell Spectra, Tower Single Phase External Battery 6 KVA Online UPS, PF = 0.8
ExTell Spectra, Tower Single Phase External Battery 10 KVA Online UPS, PF = 0.8
Downloads
FAQ’S
Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry’s standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type specimen book. It has survived not only five centuries, but also the leap into electronic typesetting, remaining essentially unchanged.